8.13.2 Connection to incremental encoder master with 24 V signal level (X3)
This interface can be used to operate the SERVOSTAR as a slave, mastered by an enco
-
der with a 24 V signal level (master-slave operation).
This uses the digital inputs DIGITAL-IN 1 and 2 on connector X3.
Frequency limit: 100 kHz, transition time tv £ 0.1 µs
8.13.3 Connection to a sine encoder master (X1)
This interface can be used to operate the SERVOSTAR as a slave, mastered by a
sine-cosine encoder (master-slave operation). This uses the SubD connector X1.
Frequency limit (A, B): 350 kHz
SERVOSTAR
®
300 Product Manual 55
Kollmorgen 09/2006 Electrical installation